System Description

  • Smoke protection for large openings in ceilings up to 65' 71/2" wide and large drop lengths (see table)

  • Flexible design provides versatile protection for challenging design situations

  • Duplex control system assures safe closing with guaranteed power supply dimensions

  • Tensioning cables spaced every five feet support large curtains and assist in withstanding pressure loads in a fire situation

  • Minimal space requirement for housing installation

  • Unique horizontal closing action

Dimensions

Clear WidthClear LengthABDH
< 4' 7"
(< 1.4m)
< 4' 11"
(< 1.5m)
4.75"
(109mm)
4.25"
(109mm)
7.5"
(190mm)
7.75"
(200 mm)
< 4' 7"
(< 1.4m)
> 14' 9"
(> 4.5m)
5.75"
(150mm)
4.25"
(109mm)
9.25"
(235mm)
11.25"
(290 mm)
< 14' 9"
(< 4.5m)
< 9' 6"
(< 2.9m)
4.75"
(120mm)
4.25"
(109mm)
7.5"
(190mm)
9.75"
(250mm)
< 14' 9"
(< 4.5m)
≥ 9' 6" - 16' 4.75"
(≥ 2.9m - < 5m)
5.75"
(150mm)
4.25"
(109mm)
9.25"
(235mm)
11.25"
(290mm)
≥ 14' 9"
(≥ 4.5m)
< 9' 6"
(< 2.9m)
4.75"
(120mm)
8.75"
(225mm)
7.5"
(190mm)
9.75"
(250mm)
≥ 14' 9" - < 98' 5"
(≥ 4.5m - < 30m)
≥ 9' 6" - < 16' 4.75"
(≥ 2.9m - < 5m)
5.75"
(150mm)
8.75"
(225mm)
9.25"
(235mm)
12.5"
(320mm)
≥ 14' 9" - < 98' 5"
(≥ 4.5m - < 30m)
>16' 4.75" - 26' 3"
(> 5m - < 8m)
5.75"
(150mm)
14"
(355mm)
10.75"
(274mm)
14"
(355mm)

Housings

Installation Options

System Types

  • Standard System: This curtain system is fail-safe and features a spring closure. It has a maximum length of 16' 5" and a maximum width of 98' 5" and may be installedunder or between the ceiling deck.

  • Cable-Free System: This is a fail-safe curtain system which requires no cables and features a spring closure. It is available in lengths up to 19' 8.25" and widths up to 19' 8.25".

  • Duplex System: This curtain is motor driven with a maximum length of 26' 3" and a maximum width of 164'.

  • Runner System: For lengths between 26' 3" and 39' 4" this curtain system is available in widths up to a 39' 4" maximum. It is motor diven, requiring an emergency backup power source, and may be installed above the ceiling deck only.

Classification

ClassificationSupercoil-H System
Automatic Smoke CurtainGuaranteed power supply
TemperatureD60
(1112° F/60 min.)
Closing SpeedSpeed ranges between 6" and 12" per second depending on system configuration

Side Guide