System Description

  • One fabric piece up to a width of 98' 5" in a range of drop lengths (see table)

  • Variable design to meet challenging construction and design problems

  • Standard drive system allows closing as a gravity fail safe system—without auxiliary power

  • Robust drive unit, applicable for a high cycle count—up to 6,000 cycles US/10,000 cycles EU

  • Typical installation requires only one motor

  • One control operates multiple curtains

  • Different levels of protection are achieved by using different types of fabrics

  • A floating bottom bar with or without safety edge is available for large widths in standard housings

  • A continuous lateral loop in the curtain is secured by the side guides and steel rods ensuring secure closure at long drop lengths and elevated curtain pressures

  • Bottom bars are warp resistant in case of high temperature

Downloads

  • Design Details

    #P06, Rev. 01, Posted 12/6/2011

    • PDF
    • DWG
    • DXF
    • DOC
  • Wiring Diagram

    #P06-E, Rev. 01, Posted 12/12/2011

    • PDF
    • DWG
    • DXF
    • DOC
  • *DWG files are in AutoCAD LT 2000 format, DOC is a Microsoft® Word format. These files are saved in .zip archives. You will need a utility to "unzip" them after download.

Dimensions

Fixed Bearing

FabricSystem WidthDrop LengthHD
EW 90/120< 16' 4.75"
(< 5 m)
≤ 6' 6.75"
(≤ 2 m)
7.5"
(190 mm)
9.75"
(250 mm)
EW 90/120< 16' 4.75"
(< 5 m)
≤ 24' 7.25"
(≤ 7.5 m)
9.25"
(235 mm)
11.25"
(290 mm)
Protex 1100< 16' 4.75"
(< 5 m)
< 13' 1.5"
(< 4 m)
7.5"
(190mm)
7.75"
(200 mm)
Protex 1100< 16' 4.75"
(< 5 m)
> 11' 5.75" - ≤ 19' 8.25"
(> 3.5 m - ≤ 6 m)
7.5"
(190 mm)
9.75"
(250 mm)
Protex 1100< 16' 4.75"
(< 5 m)
> 19' 8.25" - ≤ 29' 6.25"
(> 6 m - ≤ 9 m)
9.25"
(235 mm)
11.25"
(290 mm)
NOTE: dimensions of the housing for drop lengths 29' 61/4" (9 m) - 39' 41/4" (12 m) depend on the requested coil, consult our distributor representative for details.

Floating Bearing

FabricSystem WidthDrop LengthHD
EW 90/120< 39' 4.25"
(< 12 m)
≤ 6' 6.75"
(≤ 2 m)
7.5"
(190 mm)
9.75"
(250 mm)
EW 90/120< 39' 4.25"
(< 12 m)
≤ 19' 8.25"
(≤ 6 m)
9.25"
(235 mm)
11.25"
(290 mm)
Protex 1100< 98' 5"
(< 30 m)
< 11' 5.75"
(< 3.5 m)
7.5"
(190mm)
7.75"
(200 mm)
Protex 1100< 98' 5"
(< 30 m)
> 11' 5.75" - ≤ 19' 8.25"
(> 3.5 m - ≤ 6 m)
7.5"
(190 mm)
9.75"
(250 mm)
Protex 1100< 98' 5"
(< 30 m)
> 19' 8.25" - ≤ 29' 6.25"
(> 6 m - ≤ 9 m)
9.25"
(235 mm)
11.25"
(290 mm)
NOTE: with floating bottom bar h = at least 93/4" (250 mm).

Side Guide

TypeDrop LengthCurtain Area
80≤ 11' 5.75"
(≤ 3.5 m)
≤ 193 ft2
(≤ 18 m2)
105≤ 19' 8.25"
(≤ 6 m)
≤ 645 ft2
(≤ 60 m2)
160≤ 29' 6.25"
(≤ 9 m)
≤ 1291 ft2
(≤ 120 m2)
**R = round (standard), S = square, E = embrasure (inside opening), N = niche (recessed)

Housings

Bottom Bars

Installation Options

Protection Ratings